Page 58 - Gaylord Blue Book 2021
P. 58
ELXC SERIES
MODEL “ELXC-BBC-CL” ITEM NO. _______________
HIGH EFFICIENCY EXTRACTOR VENTILATOR
WITH CLEAN-IN-PLACE TECHNOLOGY
GENERAL SPECIFICATIONS AND DESCRIPTION
Furnish Gaylord Ventilator Model “ELXC-BBC-CL-___________” as shown
on plans and in accordance with the following specifications:
HIGH EFFICIENCY EXTRACTION: Each ventilator shall contain “XGS” High
Efficiency Extractors utilizing the “capture and drain” principle. Extractor
efficiencies shall be determined using ASTM F2519-2005 testing procedures
as accepted by ASHRAE TC 5.10 and ASHRAE Standard 154-2011 - 4.7.2.
The “capture and drain” principle shall prevent water from entering the
plenum and duct areas during “FAN ON” wash cycles, thus providing 24/7
operators the full effect of clean-in-place technology. The High Efficiency
Extractors shall not exceed 55 db, on typical cooking lines, as measured
at the chef’s ear so fatigue is minimized and productivity is optimized.
HOOD CONTROLS: Ventilator incorporates canopy mounted RTD’s
positioned strategically across the length of the hood to produce a contact
closure to react to cooking activity to comply with IMC.
CAPTURE AND CONTAINMENT: Each ventilator shall achieve capture
and containment using the lowest possible airflow rates through “passive”
versus “active” design features, thus eliminating the wiring or adjustment of APPLICATION
internal motors, plenums or jets. The ventilator shall include an integrated Wall mounted canopy for use over all types of equipment; ovens, broil-
capture wall to achieve its airflow rates. The lowest possible airflow rates ers, griddles, fryers, ranges, steam equipment, etc.
shall be tested to ASTM 1704-09 by the Food Service Technology Center
and published on their website for easy confirmation.
DESIGN FEATURES
http://www.fishnick.com/publications/appliancereports/hoods/ • Demand Control Autostart
• Internal Canopy Radius
CLEAN-IN-PLACE WASH TECHNOLOGY: Each ventilator shall include two • Enhanced “XGS” Extractor Angle and Slot Spacing
full length stainless steel wash manifolds with brass nozzles; one to power • Faceted “Super Capture”™ Lip
wash the inlet face and internal passages of the extractors during “FAN ON” • Integrated Capture Wall
mode and one to wash the plenum chamber, during the “FAN OFF” mode
as programmed by the Gaylord Command Center. Each wash manifold on OPTIONAL EQUIPMENT
each ventilator section shall operate independently so wash cycles may 1. Decorative Facings and Trim
be programmed at different frequencies and different durations to reduce 2. Demand Control Ventilation
water and detergent usage and optimize cleaning efficacy according to 3. Fire Extinguishing Systems
load and demand. Each ventilator section shall drain to sloping gutters 4. Pollution Control Systems
with 2” outlets. 5. Utility Distribution Systems
6. “XGS” Spark Arrestor Extractors
CONSTRUCTION: Each ventilator shall include full length access panels that
are non-tool entry, non-gasketed and non-removable to ease inspection of
extractors, plenum and fire extinguishing system. The ventilator shall be of
all stainless steel construction, not less than 18 gauge, type 300 series. All ACCEPTANCE & APPROVALS: Each ventilator shall include an integral
exposed surfaces shall be a number 4 finish. The use of aluminized steel or listed Demand Control Autostart fan equipment interlock complying
galvanized steel is not acceptable. The Ventilator shall include a “V” bank with IMC (optional outside North America). Each ventilator shall be
arrangement of “XGS” High Efficiency Extractors. The Ventilator shall include Listed to UL Standard 710, ULC S646 and NSF/ANSI 2, comply with all
a static pressure port in each section to be used in balancing exhaust air requirements of NFPA-96, IMC, UMC, BOCA, and SBCCI standards with
volumes. Continuous front and rear mounting brackets shall be provided XGS High Efficiency Extractors tested to ASTM 2519-2005.
to facilitate mounting to the wall and hanging from the overhead building
structure. Each duct collar shall include as standard a Gaylord Balancing
Damper (GBD) with opposed blades that adjust manually through access
from within the canopy. Ventilators built in end-to-end multiple sections
shall have as standard “Continuous Capture” from one end to the other to
ease cleaning and improve capture and containment.
LIGHT FIXTURES: The ventilator shall be equipped with:
o Recessed LED 6 Watts/Ft. Min.
o Recessed fluorescent 12 Watts/Ft. Min.
o 100 watt surface mounted incandescent 24 Watts/Ft. Min.
o 150 watt recessed incandescent 36 Watts/Ft. Min.
Light fixtures shall be factory pre-wired to a single connection point.
Ventilators built in multiple sections shall be furnished with coiled flex
conduit for interconnecting sections. GAYLORD INDUSTRIES
10900 SW AVERY ST • TUALATIN, OREGON 97062 U.S.A.
PHONE: 800.547.9696 • FAX: 503.692.6048 • email: info@gaylordventilation.com
www.gaylordventilation.com