Page 58 - Gaylord Blue Book 2021
P. 58

ELXC                         SERIES





                  MODEL “ELXC-BBC-CL”                                                  ITEM  NO. _______________

                  HIGH EFFICIENCY EXTRACTOR VENTILATOR
                    WITH CLEAN-IN-PLACE TECHNOLOGY

               GENERAL SPECIFICATIONS AND DESCRIPTION
          Furnish Gaylord Ventilator Model  “ELXC-BBC-CL-___________” as shown
          on plans and in accordance with the following specifications:

          HIGH EFFICIENCY EXTRACTION:  Each ventilator shall contain “XGS” High
          Efficiency Extractors utilizing the “capture and drain” principle.  Extractor
          efficiencies shall be determined using ASTM F2519-2005 testing procedures
          as accepted by ASHRAE TC 5.10 and ASHRAE Standard 154-2011 - 4.7.2.
          The “capture and drain” principle shall prevent water from entering the
          plenum and duct areas during “FAN ON” wash cycles, thus providing 24/7
          operators the full effect of clean-in-place technology.  The High Efficiency
          Extractors shall not exceed 55 db, on typical cooking lines, as measured
          at the chef’s ear so fatigue is minimized and productivity is optimized.
           HOOD CONTROLS:  Ventilator incorporates canopy mounted RTD’s
          positioned strategically across the length of the hood to produce a  contact
          closure to react to cooking activity to comply with IMC.
          CAPTURE AND CONTAINMENT:  Each ventilator shall achieve capture
          and containment using the lowest possible airflow rates through “passive”
          versus “active” design features, thus eliminating the wiring or adjustment of   APPLICATION
          internal motors, plenums or jets.  The ventilator shall include an integrated   Wall mounted canopy for use over all types of equipment; ovens, broil-
          capture wall to achieve its airflow rates.  The lowest possible airflow rates   ers, griddles, fryers, ranges, steam equipment, etc.
          shall be tested to ASTM 1704-09 by the Food Service Technology Center
          and published on their website for easy confirmation.
                                                                     DESIGN FEATURES
             http://www.fishnick.com/publications/appliancereports/hoods/  •  Demand Control Autostart
                                                                       •  Internal Canopy Radius
          CLEAN-IN-PLACE WASH TECHNOLOGY:  Each ventilator shall include two   •  Enhanced “XGS” Extractor Angle and Slot Spacing
          full length stainless steel wash manifolds with brass nozzles; one to power   •  Faceted “Super Capture”™ Lip
          wash the inlet face and internal passages  of the extractors during “FAN ON”   •  Integrated Capture Wall
          mode and one to wash the plenum chamber, during the “FAN OFF” mode
          as programmed by the Gaylord Command Center.  Each wash manifold on   OPTIONAL EQUIPMENT
          each ventilator section shall operate independently so wash cycles may   1. Decorative Facings and Trim
          be programmed at different frequencies and different durations to reduce   2. Demand Control Ventilation
          water and detergent usage and optimize cleaning efficacy according to   3. Fire Extinguishing Systems
          load and demand.  Each ventilator section shall drain to sloping gutters   4. Pollution Control Systems
          with 2” outlets.                                             5. Utility Distribution Systems
                                                                       6. “XGS” Spark Arrestor Extractors
          CONSTRUCTION:  Each ventilator shall include full length access panels that
          are non-tool entry, non-gasketed and non-removable to ease inspection of
          extractors, plenum and fire extinguishing system.  The ventilator shall be of
          all stainless steel construction, not less than 18 gauge, type 300 series. All   ACCEPTANCE & APPROVALS:   Each ventilator shall include an integral
          exposed surfaces shall be a number 4 finish. The use of aluminized steel or   listed Demand Control Autostart fan equipment interlock complying
          galvanized steel is not acceptable.  The Ventilator shall include a “V” bank   with IMC (optional outside North America).  Each ventilator shall be
          arrangement of “XGS” High Efficiency Extractors.  The Ventilator shall include   Listed to UL Standard 710, ULC S646 and NSF/ANSI 2, comply with all
          a static pressure port in each section to be used in balancing exhaust air   requirements of NFPA-96, IMC, UMC, BOCA, and SBCCI standards  with
          volumes.  Continuous front and rear mounting brackets shall be provided   XGS High Efficiency Extractors tested to ASTM 2519-2005.
          to facilitate mounting to the wall and hanging from the overhead building
          structure.  Each duct collar shall include as standard a Gaylord Balancing
          Damper (GBD) with opposed blades that adjust manually through access
          from within the canopy.  Ventilators built in end-to-end multiple sections
          shall have as standard “Continuous Capture” from one end to the other to
          ease cleaning and improve capture and containment.
          LIGHT FIXTURES: The ventilator shall be equipped with:

          o Recessed LED                        6 Watts/Ft. Min.
          o Recessed fluorescent              12 Watts/Ft. Min.
          o 100 watt surface mounted incandescent   24 Watts/Ft. Min.
          o 150 watt recessed incandescent      36 Watts/Ft. Min.
          Light  fixtures shall  be  factory  pre-wired  to  a single connection  point.
          Ventilators built in multiple sections shall be furnished with coiled flex
          conduit for interconnecting sections.                            GAYLORD INDUSTRIES